UPS Runtime Estimator
Calculate how long your UPS battery will power your devices during an outage. Enter your battery specifications and load to get an estimated backup runtime.
Battery & Load Parameters
Rated capacity of your UPS battery in ampere-hours
Total batteries connected in series
Combined power draw of all connected devices
Typical range: 85-95% (check your UPS manual)
Recommended: 50% for lead-acid, 80% for Li-ion
Estimated Runtime
Estimated Backup Time
--
hours
Total Energy
-- Wh
Usable Energy
-- Wh
Runtime (min)
-- min
Load %
-- %
⚠️
Quick Presets
How to Calculate UPS Battery Runtime
The UPS runtime estimation is based on the following formula:
Runtime (hrs) = (Battery Voltage × Battery Ah × No. of Batteries × DoD × Efficiency) ÷ Load Watts
Step-by-Step Process:
- Determine your battery voltage (V)
- Find battery capacity in Ah (on label)
- Count total batteries in the UPS
- Add up all device wattages
- Check UPS efficiency rating
- Apply formula or use our calculator
Example Calculation:
- Battery: 12V, 100Ah, ×2 batteries
- Load: 300W
- Efficiency: 90%, DoD: 80%
- Total Wh = 12 × 100 × 2 = 2400 Wh
- Usable Wh = 2400 × 0.80 × 0.90 = 1728 Wh
- Runtime = 1728 ÷ 300 = 5.76 hours